Reliance Electric 45C-766(45C766)8‑channel isolated relay output module
Description
Product Introduction
Model Interpretation
45C = Family code for Reliance Electric AutoMax/AutoMate/Shark XL series I/O modules.
766 = 8‑channel isolated relay output module; “7” denotes high‑current isolated relay, “66” relates to output configuration.
(‑) = Common separator in ordering; functionally identical to 45C766.
Alternate 45CRLY / HE45C‑RLY = Horner Electric equivalent part number.
Technical Parameters
Outputs: 8 independent, electrically isolated normally open (N.O.) relay channels.
Rated voltage: 250 VAC, 125/250 VDC.
Rated current: 10 A per channel resistive (AC), 5 A per channel (DC).
Min switching load: 100 mA @ 5 VDC.
Isolation: 2,500 Vrms between channels and logic; channel‑to‑channel isolation.
Fuses: Individual replaceable fuses per channel (AGC type, 5 A / 250 V).
Indicators: Power LED, 8 channel ON LEDs, 8 fuse‑fault LEDs on front panel.
Operating temperature: ‑20 °C to +60 °C.
Protection class: IP20 (cabinet use).
Mounting: 45C‑series DIN rail.
Terminals: 18‑position screw terminal strip (two rows of nine).
Certification: CE, UL listed for industrial control.
Mechanical life: >100,000 operations per relay.
Interface and Communication Configuration
Backplane connection: Plug‑in to Shark XL / AutoMax backplane for power and logic I/O.
Field wiring: Front‑panel 18‑position screw terminals for eight relay common and normally open contacts.
Communication: Backplane bus only; no external serial/network ports.
Compatibility: Shark XL, AutoMax, AutoMate PLC systems; 45C‑series I/O rail (up to 8 modules per rail).
Core Functions
Converts controller logic signals into 8‑channel isolated relay switching for high‑current loads.
Provides galvanic isolation between control system and field devices to suppress noise and protect circuitry.
Individual channel fuses offer overcurrent protection per output.
LED status enables real‑time diagnostics for power, channel state, and fuse faults.
Hot‑swap capable (with system power removed) for easy replacement.
Application Scenarios
Industrial automation: Driving contactors, motor starters, solenoid valves, heaters, and large indicator lamps.
Process control: 120/230 VAC or 24/48/110 VDC high‑current switching on production lines, machine tools, packaging, and material handling equipment.
Panel‑building: Isolated, multi‑channel output for OEM panels requiring robust load driving and safety isolation.
Operation and Maintenance Instructions
Install on a 45C‑series DIN rail and ensure full backplane engagement before powering on.
Torque all field wiring terminals to manufacturer specifications; verify insulation integrity.
During operation, monitor front‑panel LEDs: power ON, channel LEDs follow command state, fuse LEDs OFF for normal operation.
If a fuse LED illuminates, power down the system, replace the corresponding AGC 5 A / 250 V fuse, and inspect wiring for shorts.
Keep the module surface clean and free of dust to maintain proper heat dissipation.
Disconnect system power before removal, inspection, or replacement.
Do not disassemble internal components; replace the entire module if a permanent fault occurs.
The unit is discontinued by Reliance Electric; use surplus or refurbished units for replacement.
Get a Quote