Technical Parameters
Configuration: 16 channels (SDI), SIL2 (16ch) / SIL3 (8ch) configurable
Input: 24 VDC, 1‑wire, sink/source, 2 mA input current
Safety: IEC 61508 SIL2/SIL3, EN 954‑1 Category 4
Isolation: 2500 V AC between field and backplane
Response Time: ≤ 1 ms (safety‑critical signals)
Pulse Input: 8 channels support pulse counting (max 10 kHz)
Power: 24 V DC ±10%, ≤ 2.5 W
Operating Temperature: ‑40°C to +85°C (industrial extended range)
Protection: IP20
Dimensions (W×H×D): 67.5 mm × 76 mm × 62 mm
Weight: 0.122 kg
Mounting: 35 mm DIN rail.
Interface & Communication
Wiring: Screw terminals (16 input channels + common)
Backplane: AC500 safety bus (direct connection to CPU)
Protocols: PROFIBUS DP, PROFINET, Modbus RTU (via PLC)
LEDs: PWR (green), RUN (yellow), 16×CH (yellow), FAULT (red), SAFE (green).
Core Functions
Safety Input: 16‑channel 24 VDC safety signal monitoring (emergency stop, safety gates, light curtains)
SIL Mode Selection: Software switch between 16×SIL2 or 8×SIL3
Pulse Counting: 8 channels for safety‑related pulse signals (encoders, flow meters)
Diagnostics: Short‑circuit, open‑circuit, overvoltage, and temperature monitoring
Safety Voting: Supports 1oo2/2oo2 voting for high‑safety applications.
Application Scenarios
Safety Instrumented Systems (SIS): Emergency shutdown (ESD), safety interlocks
Machine Safety: Safety gate monitoring, light curtains, emergency stop circuits
Process Automation: SIL2/SIL3‑rated signal acquisition in chemical, oil & gas
Packaging & Material Handling: Safety‑critical conveyor and machine guarding.
Operation & Maintenance
Installation: DIN rail mount; 20 mm clearance for cooling
Wiring: Shielded cables for safety signals; separate from power wires; torque 0.5–0.6 Nm
Configuration: Automation Builder/CoDeSys for SIL mode and channel parameters
Maintenance: Periodic terminal check; clean with dry cloth
Troubleshooting: No PWR → 24 V supply; RUN flash → config error; CH alarm → field wiring fault; SAFE off → safety channel tripped.