ABB 1SAP140200R0100(PM582)high‑performance compact CPU module
Description
Product Introduction
Model Explanation
PM582: Denotes the enhanced CPU series within AC500.
R0100: Specifies the hardware revision.
It belongs to the ABB AC500 PLC line and is fully compatible with the series’ terminal bases, I/O modules, and FBP communication accessories.
Technical Parameters
Power supply: 24 V DC (20.4–28.8 V DC), power consumption approx. 9 W.
Memory: 512 kB flash for user programs, 832 kB RAM for data, 64 kB retentive data memory.
Processing speed: 0.05 μs/bit instruction, 0.07 μs/word instruction, 1.6 μs/floating‑point instruction.
Operating temperature: 0 °C to +60 °C; storage temperature: ‑40 °C to +70 °C.
Protection class: IP20; certifications: CE, cULus, RoHS.
Dimensions: 62 × 76 × 67.5 mm; weight approx. 0.16 kg.
Interface and Communication Configuration
Serial ports: 2 × configurable (COM1: RS232/RS485; COM2: RS485), supporting Modbus RTU, CS31, ASCII; COM1 acts as CS31 master for distributed I/O.
SD card slot: For program backup/restore, firmware updates, and data logging.
Local operation: LCD with physical keys for status display, parameter setting, and fault diagnosis without a PC.
FBP interface: Supports optional fieldbus modules (e.g., Profibus DP, CANopen, Ethernet) for extended connectivity.
Core Functions
Efficiently executes complex logic, process control, and motion control tasks with larger program memory.
Multi‑protocol serial and FBP‑based communication enables seamless connection with HMIs, drives, instruments, and SCADA systems.
Local LCD/keys simplify on‑site operation and maintenance.
Supports large‑scale I/O expansion: up to 320 digital inputs, 240 digital outputs, 160 analog inputs, 160 analog outputs.
Hot‑swap of expansion modules reduces downtime.
SD card enables fast program backup and offline firmware upgrades.
Application Scenarios
Factory automation: Complex production lines, robotics, high‑speed packaging, and machine tools.
Process industries: Water treatment, HVAC, chemical, pharmaceutical, and food & beverage requiring larger logic capacity.
Infrastructure: Intelligent building control, energy management, and medium‑size power distribution automation.
System upgrades: Ideal for modernizing legacy systems with higher memory and processing demands.
Usage and Maintenance Instructions
Mount on a standard DIN rail (TH35‑15) and connect 24 V DC power correctly.
Install the matching terminal base and required I/O modules; connect serial and FBP communication cables.
Configure parameters and download programs via ABB Automation Builder before commissioning.
Keep the environment ventilated and dry; ensure all terminals are tightened.
Back up programs regularly using the SD card.
Perform quarterly routine inspections and annual comprehensive tests.
Disconnect power before disassembly or replacement to ensure safety.