086351-004 Application Controller (BACnet/IP)
Description
Product Introduction
Model Explanation
086351: Base part number for ABB T‑series BMS controllers
‑004: Standard hardware revision, 2×Ethernet + 1×RS‑485, conformal coated
Type: BMS Application Controller
Platform: ABB T3000, T2000 BMS
Mounting: 35mm DIN rail, IP20 rated
Technical Parameters
Processor: 32‑bit embedded CPU
Power Supply: 24 V AC/DC ±20%
Power Consumption: <15 W (typical)
Communication:
2×10/100 Mbps Ethernet (RJ45, BACnet/IP)
1×RS‑485 (BACnet MS/TP, master)
Modbus RTU (slave)
Programming: T3000 Workbench, JavaScript scripting
Functions: Scheduling, trend logging, alarm management, energy accumulation
Web Interface: Embedded HTML5, remote access
Dimensions: 120 × 45 × 115 mm (H×W×D)
Weight: ~0.4 kg
Operating Temperature: ‑10 °C to +50 °C
Storage Temperature: ‑25 °C to +70 °C
Humidity: 5%–95% non‑condensing
Certifications: CE, UL, RoHS
Core Functions
Centralized BMS Control: Coordinates HVAC, lighting, access control, and fire alarm systems
BACnet Interoperability: Native BACnet/IP & MS/TP for seamless integration with third‑party devices
Embedded Web Server: HTML5 dashboard for remote monitoring, configuration, and troubleshooting
Energy Optimization: Scheduling, load shedding, and trend analysis to reduce consumption
Alarm & Event Management: Real‑time alerts, historical logging, and email notifications
Scriptable Logic: JavaScript support for custom control sequences and complex automation
Application Scenarios
Commercial Buildings: Office towers, shopping malls, hotels
Public Facilities: Hospitals, airports, schools, data centers
Industrial Sites: Factory HVAC, cleanrooms, energy monitoring
Retrofit Projects: Upgrading legacy BMS with modern IP‑based control
Usage & Maintenance
Installation: DIN rail mount; ensure proper ventilation (≥50 mm clearance)
Wiring: Separate AC/DC power from communication cables; use shielded twisted pair for RS‑485
Configuration: Assign static IP; configure BACnet network via T3000 Workbench
Maintenance: Monthly LED status check; quarterly backup; annual firmware update
Replacement: Use identical 086351‑004; restore configuration from backup
Get a Quote