ABB 07KT98‑S(GJR5253100R0260)safety‑certified CPU
Description
Product Introduction
Model Explanation
07: Procontic 90 / AC31 series platform
KT: CPU with DC transistor outputs
98: High‑capacity basic controller grade
‑S: Safety‑certified variant (SIL 2/PL d, safety I/O & logic)
‑ARCNET: Onboard ARCNET for safety‑related real‑time communication
Technical Parameters
Part Number: GJR5253100R0260
Processor: 32‑bit RISC (same as 07KT98)
Power Supply: 24 VDC (18–30 VDC), ≤22 W, reverse polarity protection
Memory: 1 MB Flash (program); 1 MB RAM (data); 256 kB non‑volatile RETAIN (safety recipes/critical data)
Onboard Digital I/O: 24 × 24 VDC DI (isolated, 3 groups); 16 × transistor DO (24 VDC/0.5 A, isolated, 2 groups, short‑circuit protected)
Safety I/O: Dedicated safety‑related DI/DO for SIL 2/PL d circuits (emergency stop, safety interlocks)
Onboard Analog I/O: 8 × 12‑bit AI (configurable 0–10 V/±10 V/4–20 mA/PT100); 4 × 12‑bit AO (configurable 0–10 V/4–20 mA)
High‑Speed Counter: 2 × 50 kHz (hardware, 7 modes)
Safety Certification: SIL 2 (IEC 61508), PL d (EN ISO 13849‑1)
Operating Temperature: 0°C to +55°C (standard industrial; extended ‑25°C to +70°C on request)
Storage Temperature: -40°C to +85°C
Protection Class: IP20
Dimensions: 180 × 100 × 95 mm
Weight: ≈1.0 kg
Certifications: CE, UL, CSA, RoHS, safety‑related EMC compliance
Interface & Communication Configuration
ARCNET: Onboard (standard) for deterministic safety networking (real‑time safety data exchange)
COM1: RS‑232 for programming, HMI, safety data logging
COM2: RS‑485 for Modbus RTU, CS31 system bus (safety I/O expansion)
CS31 System Bus: Up to 31 remote I/O slaves (including safety I/O modules)
Ethernet: Optional 10/100 Mbps for non‑safety communication (Modbus TCP/IP)
Safety Protocol: ARCNET for safety‑critical data (redundant, deterministic)
LED Indicators: PWR, RUN, ERR, SAFE (safety status), TX/RX (RS‑485), NET (ARCNET)
Programming Tool: Control Builder AC31 + Safetyconf (safety logic configuration)
RTC: Integrated for safety event time‑stamping
Storage: SmartMedia card for program/safety logic backup
Core Functions
Functional Safety (SIL 2/PL d): Dedicated safety I/O and logic for emergency stop, safety doors, and process safety; certified per IEC 61508/EN ISO 13849‑1.
Large Safety‑Optimized Memory: 1 MB program + 1 MB data + 256 kB RETAIN supports complex safety algorithms and recipe storage.
High‑Density Mixed I/O: 24DI/16DO + 8AI/4AO plus dedicated safety I/O for integrated safety and standard control.
Deterministic ARCNET Safety Network: Onboard ARCNET for real‑time, redundant safety communication between controllers.
Multi‑Protocol Comms: ARCNET (safety), Ethernet (non‑safety), Modbus RTU, CS31 for seamless integration.
Safety Data Retention: 256 kB RETAIN preserves safety‑critical data during power cycles.
Safetyconf Configuration: Dedicated software for safety logic setup, validation, and diagnostics.
Application Scenarios
Safety‑Critical Process Control: Chemical, oil/gas, pharmaceutical plants (SIL 2/PL d safety loops).
Machine Safety: Packaging, automotive assembly, robotics (emergency stop, safety interlocks).
Distributed Safety Systems: Factory‑wide safety networks via ARCNET, remote safety I/O monitoring.
Legacy Safety System Upgrades: Replacing older AC31 safety CPUs with higher memory/performance.
Water/Wastewater Safety: Pump station interlocks, overflow protection, emergency shutdowns.
Usage & Maintenance Instructions
Installation: DIN rail mount; 50 mm clearance for ventilation; separate safety/standard wiring.
Wiring: Shielded cables for ARCNET/Ethernet; safety I/O cables routed separately; torque terminals 0.5–0.8 Nm.
Power‑On Check: Verify 24 VDC; PWR LED steady on; SAFE LED green (safety logic OK); ERR LED off.
Programming: Use Control Builder AC31 + Safetyconf; download safety logic via ARCNET/Ethernet; validate safety logic before deployment.
Routine Maintenance: Quarterly safety I/O continuity check; clean vents every 6 months; monitor SAFE/ERR LEDs.
Troubleshooting: SAFE LED red = safety fault (check interlocks/wiring); ARCNET faults = verify cables/addresses; I/O errors = check safety sensor/actuator wiring.
Environment: Operate 0°C to +55°C, 5%–95% non‑condensing humidity; avoid corrosive gases.
Replacement: Disconnect power; use identical 07KT98‑S; reconfigure safety logic/ARCNET parameters via Safetyconf.
Get a Quote