ABB 07KP96 PDnet coupler module for the AC31/Advant OCS control system
Description
Product Introduction
Model Explanation
07: AC31 / Procontic 90 series platform
KP: Communication Processor / Coupler
96: PDnet coaxial bus coupler version
Ordering Number: GATS110112R0001 (standard)
Technical Parameters
Power Supply: 24 VDC ±10%
Current Consumption: ~380 mA
Processor: 32‑bit industrial MCU
Memory: 4 MB Flash, 1 MB RAM
Bus Type: PDnet (coaxial cable)
Transmission Rate: 2 Mbps (fixed)
Network Topology: Single or redundant PDnet
Data Capacity: Up to 512 data points (8 bits each)
Operating Temperature: -10 °C to +60 °C
Storage Temperature: -40 °C to +85 °C
Isolation: 1500 VAC (bus to backplane)
Dimensions (W×H×D): 51 × 110 × 75 mm
Weight: Approx. 0.55 kg
Certifications: CE, RoHS, UL 508
Interface and Communication Configuration
PDnet Bus: BNC connector for coaxial cable; supports redundant bus operation.
Configuration Port: Mini‑USB (local setup via AC31 Control Builder).
LED Indicators:
PWR (green): Power OK
COM (yellow): PDnet bus activity
ERR (red): Bus fault, config error or timeout
Wiring: 75 Ω coaxial cable; termination at both ends (75 Ω).
Core Functions
PDnet Bus Coupling: Connects AC31 to PDnet coaxial network (2 Mbps).
Redundant Communication: Supports dual‑bus PDnet for high availability.
High‑Speed Data Exchange: Transfers up to 512 process data points.
Physical Layer Conversion: Converts AC31 internal bus to PDnet coaxial.
Diagnostics & Monitoring: Real‑time LED and software diagnostics.
Application Scenarios
Process Automation: Power plants, chemical, water treatment with PDnet I/O and drives.
Legacy System Integration: Migrating PDnet devices into AC31/Advant OCS.
High‑Speed I/O Networks: Factories requiring deterministic 2 Mbps process data.
Redundant Control Systems: Critical lines with dual PDnet bus for zero downtime.
Usage and Maintenance Instructions
Installation: Mount on 35 mm DIN rail or AC31 rack.
Wiring: 24 VDC power; 75 Ω coaxial for PDnet; 75 Ω termination at bus ends.
Configuration: Set PDnet address, redundancy mode via Control Builder.
Routine Check: Verify LEDs quarterly; inspect cables/connections annually.
Troubleshooting: Check power/wiring; confirm termination; re‑download config if errors pers
Get a Quote